西门子PLC
西门子ET200S模拟量模块PLC
点击次数:42  发布时间:2018-03-19

西门子ET200S模拟量模块PLC


ET200S模拟量模块西门子PLC概述:

  • 模拟量输入和输出,用于 ET 200S

  • 采用自动编码,可插入到 TM-E 端子模板

  • 高性能型具有增强的功能、精度和分辨率

  • 高速型具有极快的速度、同步周期时间

  • 可以进行模板的热交换

注:

请查找组态指南,了解如何选择合适的 TM-E 端子模块。

 

技术规范

Article number

6ES7134-4FB01-0AB0

6ES7134-4LB02-0AB0

6ES7134-4GB01-0AB0

6ES7134-4GB52-0AB0

 

ET200S, EL-MOD., 2AI STD U, +/-10V,1-5V

ET200S, EL-MOD., 2AI U HF, +/-10V, 1..5V

ET200S, EL-MOD., 2AI STD I-2DMU, 0-20MA,

ET200S, EL-MOD., 2AI HS I-2DMU, 0-20MA,

Supply voltage

       

Load voltage L+

       
  • ● Rated value (DC)

24 V; From power module

24 V

24 V; From power module

24 V

  • ● Short-circuit protection

     

Yes

  • ● Reverse polarity protection

Yes

Yes

Yes; Destruction limit 35 mA per channel

Yes

Input current

       

from load voltage L+ (without load), max.

30 mA

55 mA

80 mA

225 mA

from backplane bus 3.3 V DC, max.

10 mA

10 mA

10 mA

10 mA

Output voltage

       

Power supply to the transmitters

       
  • ● present

 

No

 

Yes

  • ● short-circuit proof

     

Yes

Power loss

       

Power loss, typ.

0.6 W

0.85 W

0.6 W

2.5 W

Address area

       

Address space per module

       
  • ● Address space per module, max.

4 byte

4 byte

4 byte

4 byte

Analog inputs

       

Number of analog inputs

2

2

2

2

permissible input voltage for voltage input (destruction limit), max.

35 V; 35 V continuous; 75 V for max. 1 ms (mark to space ratio 1:20)

35 V; 35 V continuous; 75 V for max. 1 ms

   

permissible input current for current input (destruction limit), max.

   

40 mA

 

Cycle time (all channels) max.

Number of active channels per module x basic conversion time

0.5 ms; 0.5 ms for 2 channels without noise suppression, 18 / 21 ms per channel with noise suppression

Number of active channels per module x basic conversion time

0.25 ms

Input ranges

       
  • ● Voltage

Yes

Yes

No

No

  • ● Current

No

No

Yes

Yes

  • ● Thermocouple

No

No

No

No

  • ● Resistance thermometer

No

No

No

No

  • ● Resistance

No

No

No

No

Input ranges (rated values), voltages

       
  • ● 1 V to 5 V

Yes

Yes

   
  • ● Input resistance (1 V to 5 V)

 

800 kΩ

   
  • ● -10 V to +10 V

Yes

Yes

   
  • ● Input resistance (-10 V to +10 V)

 

800 kΩ

   
  • ● -5 V to +5 V

Yes

Yes

   
  • ● Input resistance (-5 V to +5 V)

 

800 kΩ

   

Input ranges (rated values), currents

       
  • ● 0 to 20 mA

     

Yes

  • ● Input resistance (0 to 20 mA)

     

106 Ω

  • ● 4 mA to 20 mA

   

Yes; on 50 ohms

Yes

Cable length

       
  • ● shielded, max.

200 m

200 m

200 m

200 m

Analog value generation for the inputs

       

Measurement principle

integrating

 

integrating

 

Integration and conversion time/resolution per channel

       
  • ● Resolution with overrange (bit including sign), max.

14 bit; +/-10 V: 13 bits + sign, +/-5 V: 13 bits + sign; 1 to 5 V: 13 bits

16 bit; 0 to 5 V: 15 bits, +/-10 V: 16 bits, +/-5 V: 16 bits

13 bit; 4 to 20 mA: 13 bits

16 bit

  • ● Integration time, parameterizable

Yes

Yes

   
  • ● Integration time (ms)

16,7 / 20 ms

 

16,7 / 20 ms

 
  • ● Interference voltage suppression for interference frequency f1 in Hz

50 / 60 Hz

60 / 50 Hz / no

50 / 60 Hz

 
  • ● Conversion time (per channel)

65 ms; 55 / 65 ms

0.04 ms; Without noise suppression 17/20 ms per channel with error

65 ms; 55 / 65 ms

 

Smoothing of measured values

       
  • ● parameterizable

Yes; In four stages by means of digital filtering

Yes; In 4 stages: 1 x, 4 x, 16 x, 32 x cycle time

Yes; In four stages by means of digital filtering

Yes

  • ● Step: None

Yes; 1 x cycle time

Yes; 1x

Yes; 1 x cycle time

Yes; 1 x cycle time

  • ● Step: low

Yes; 4 x cycle time

Yes; 4x

Yes; 4 x cycle time

Yes; 4 x cycle time

  • ● Step: Medium

Yes; 32 x cycle time

Yes; 16x

Yes; 32 x cycle time

Yes; 16 x cycle time

  • ● Step: High

Yes; 64 x cycle time

Yes; 32x

Yes; 64 x cycle time

Yes; 32 x cycle time

Encoder

       

Connection of signal encoders

       
  • ● for voltage measurement

 

Yes

   
  • ● for current measurement as 2-wire transducer

     

Yes

  • — Burden of 2-wire transmitter, max.

   

750 Ω

 

Errors/accuracies

       

Linearity error (relative to input range), (+/-)

0.01 %

0.01 %

0.01 %

0.03 %

Temperature error (relative to input range), (+/-)

0.01 %/K

0.003 %/K

0.005 %/K

0.01 %/K

Crosstalk between the inputs, min.

-50 dB

-100 dB

-50 dB

50 dB

Repeat accuracy in steady state at 25 °C (relative to input range), (+/-)

0.05 %

0.01 %

0.05 %

0.1 %

Operational error limit in overall temperature range

       
  • ● Voltage, relative to input range, (+/-)

0.6 %

0.1 %; 0.2% without interference frequency suppression

   
  • ● Current, relative to input range, (+/-)

   

0.6 %

0.3 %

Basic error limit (operational limit at 25 °C)

       
  • ● Voltage, relative to input range, (+/-)

0.4 %

0.05 %; 0.1% without interference frequency suppression

   
  • ● Current, relative to input range, (+/-)

   

0.4 %

0.2 %

Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency

       
  • ● Series mode interference (peak value of interference < rated value of input range), min.

70 dB

90 dB

70 dB

 
  • ● Common mode interference (USS < 2.5 V) , min.

90 dB

100 dB

   

Isochronous mode

       

Isochronous operation (application synchronized up to terminal)

No

Yes

No

Yes

Interrupts/diagnostics/status information

       

Alarms

       
  • ● Hardware interrupt

 

Yes

 

Yes

Diagnostic messages

       
  • ● Wire-break

Yes; Measuring range 1 to 5 V only

Yes; Measuring range 1 to 5 V only

Yes

Yes; at 4 to 20 mA

  • ● Group error

Yes

Yes

Yes

Yes

  • ● Overflow/underflow

Yes

Yes

Yes

Yes

Diagnostics indication LED

       
  • ● Group error SF (red)

Yes

Yes

Yes

Yes

Parameter

       

Remark

4 byte

12 bytes, 4 bytes in compatibility mode

4 byte

 

Diagnostics wire break

Disable / enable (only in measuring range 1 to 5 V)

   

At 4 to 20 mA

Measurement type/range

deactivated / +/-5 V / 1 to 5 V / +/-10 V

deactivated / +/-5 V / 1 to 5 V / +/-10 V

deactivated / 4 to 20 mA

4 to 20 mA, 0 to 20 mA

Group diagnostics

Disable / enable

Disable / enable

Disable / enable

1

Overflow/underflow

Disable / enable

Disable / enable

Disable / enable

1

Potential separation

       

Potential separation analog inputs

       
  • ● between the channels

No

No; however, increased permissible potential difference between the inputs.

No

No

  • ● between the channels and backplane bus

Yes

Yes

Yes

Yes

  • ● Between the channels and load voltage L+

Yes

Yes

No

Yes

Permissible potential difference

       

between the inputs (UCM)

 

140 V DC/100 V AC

   

Between the inputs and MANA (UCM)

2 V AC PP

     

between MANA and M internally (UISO)

75 V DC/60 V AC

   

75 V DC/60 V AC

Isolation

       

Isolation tested with

500 V DC

500 V DC

500 V DC

 

Dimensions

       

Width

15 mm

15 mm

15 mm

15 mm

Height

81 mm

81 mm

81 mm

81 mm

Depth

52 mm

52 mm

52 mm

52 mm

Weights

       

Weight, approx.

40 g

45 g

40 g


相关产品:西门子PLC 

  • QQ咨询

  • 在线咨询
  • 点击这里给我发消息
友情链接: 工控文章