联系人:周经理
电话:025-85951615
手机:18551776358
邮编:210000
邮箱:2964320295@qq.com
地址:南京市江宁区诚信大道998号5栋
ET200S模拟量模块西门子PLC概述:
-
模拟量输入和输出,用于 ET 200S
-
采用自动编码,可插入到 TM-E 端子模板
-
高性能型具有增强的功能、精度和分辨率
-
高速型具有极快的速度、同步周期时间
-
可以进行模板的热交换
注:
请查找组态指南,了解如何选择合适的 TM-E 端子模块。
技术规范
Article number |
6ES7134-4FB01-0AB0 |
6ES7134-4LB02-0AB0 |
6ES7134-4GB01-0AB0 |
6ES7134-4GB52-0AB0 |
|
---|---|---|---|---|---|
|
ET200S, EL-MOD., 2AI STD U, +/-10V,1-5V |
ET200S, EL-MOD., 2AI U HF, +/-10V, 1..5V |
ET200S, EL-MOD., 2AI STD I-2DMU, 0-20MA, |
ET200S, EL-MOD., 2AI HS I-2DMU, 0-20MA, |
|
Supply voltage |
|||||
Load voltage L+ |
|||||
|
24 V; From power module |
24 V |
24 V; From power module |
24 V |
|
|
Yes |
||||
|
Yes |
Yes |
Yes; Destruction limit 35 mA per channel |
Yes |
|
Input current |
|||||
from load voltage L+ (without load), max. |
30 mA |
55 mA |
80 mA |
225 mA |
|
from backplane bus 3.3 V DC, max. |
10 mA |
10 mA |
10 mA |
10 mA |
|
Output voltage |
|||||
Power supply to the transmitters |
|||||
|
No |
Yes |
|||
|
Yes |
||||
Power loss |
|||||
Power loss, typ. |
0.6 W |
0.85 W |
0.6 W |
2.5 W |
|
Address area |
|||||
Address space per module |
|||||
|
4 byte |
4 byte |
4 byte |
4 byte |
|
Analog inputs |
|||||
Number of analog inputs |
2 |
2 |
2 |
2 |
|
permissible input voltage for voltage input (destruction limit), max. |
35 V; 35 V continuous; 75 V for max. 1 ms (mark to space ratio 1:20) |
35 V; 35 V continuous; 75 V for max. 1 ms |
|||
permissible input current for current input (destruction limit), max. |
40 mA |
||||
Cycle time (all channels) max. |
Number of active channels per module x basic conversion time |
0.5 ms; 0.5 ms for 2 channels without noise suppression, 18 / 21 ms per channel with noise suppression |
Number of active channels per module x basic conversion time |
0.25 ms |
|
Input ranges |
|||||
|
Yes |
Yes |
No |
No |
|
|
No |
No |
Yes |
Yes |
|
|
No |
No |
No |
No |
|
|
No |
No |
No |
No |
|
|
No |
No |
No |
No |
|
Input ranges (rated values), voltages |
|||||
|
Yes |
Yes |
|||
|
800 kΩ |
||||
|
Yes |
Yes |
|||
|
800 kΩ |
||||
|
Yes |
Yes |
|||
|
800 kΩ |
||||
Input ranges (rated values), currents |
|||||
|
Yes |
||||
|
106 Ω |
||||
|
Yes; on 50 ohms |
Yes |
|||
Cable length |
|||||
|
200 m |
200 m |
200 m |
200 m |
|
Analog value generation for the inputs |
|||||
Measurement principle |
integrating |
integrating |
|||
Integration and conversion time/resolution per channel |
|||||
|
14 bit; +/-10 V: 13 bits + sign, +/-5 V: 13 bits + sign; 1 to 5 V: 13 bits |
16 bit; 0 to 5 V: 15 bits, +/-10 V: 16 bits, +/-5 V: 16 bits |
13 bit; 4 to 20 mA: 13 bits |
16 bit |
|
|
Yes |
Yes |
|||
|
16,7 / 20 ms |
16,7 / 20 ms |
|||
|
50 / 60 Hz |
60 / 50 Hz / no |
50 / 60 Hz |
||
|
65 ms; 55 / 65 ms |
0.04 ms; Without noise suppression 17/20 ms per channel with error |
65 ms; 55 / 65 ms |
||
Smoothing of measured values |
|||||
|
Yes; In four stages by means of digital filtering |
Yes; In 4 stages: 1 x, 4 x, 16 x, 32 x cycle time |
Yes; In four stages by means of digital filtering |
Yes |
|
|
Yes; 1 x cycle time |
Yes; 1x |
Yes; 1 x cycle time |
Yes; 1 x cycle time |
|
|
Yes; 4 x cycle time |
Yes; 4x |
Yes; 4 x cycle time |
Yes; 4 x cycle time |
|
|
Yes; 32 x cycle time |
Yes; 16x |
Yes; 32 x cycle time |
Yes; 16 x cycle time |
|
|
Yes; 64 x cycle time |
Yes; 32x |
Yes; 64 x cycle time |
Yes; 32 x cycle time |
|
Encoder |
|||||
Connection of signal encoders |
|||||
|
Yes |
||||
|
Yes |
||||
|
750 Ω |
||||
Errors/accuracies |
|||||
Linearity error (relative to input range), (+/-) |
0.01 % |
0.01 % |
0.01 % |
0.03 % |
|
Temperature error (relative to input range), (+/-) |
0.01 %/K |
0.003 %/K |
0.005 %/K |
0.01 %/K |
|
Crosstalk between the inputs, min. |
-50 dB |
-100 dB |
-50 dB |
50 dB |
|
Repeat accuracy in steady state at 25 °C (relative to input range), (+/-) |
0.05 % |
0.01 % |
0.05 % |
0.1 % |
|
Operational error limit in overall temperature range |
|||||
|
0.6 % |
0.1 %; 0.2% without interference frequency suppression |
|||
|
0.6 % |
0.3 % |
|||
Basic error limit (operational limit at 25 °C) |
|||||
|
0.4 % |
0.05 %; 0.1% without interference frequency suppression |
|||
|
0.4 % |
0.2 % |
|||
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency |
|||||
|
70 dB |
90 dB |
70 dB |
||
|
90 dB |
100 dB |
|||
Isochronous mode |
|||||
Isochronous operation (application synchronized up to terminal) |
No |
Yes |
No |
Yes |
|
Interrupts/diagnostics/status information |
|||||
Alarms |
|||||
|
Yes |
Yes |
|||
Diagnostic messages |
|||||
|
Yes; Measuring range 1 to 5 V only |
Yes; Measuring range 1 to 5 V only |
Yes |
Yes; at 4 to 20 mA |
|
|
Yes |
Yes |
Yes |
Yes |
|
|
Yes |
Yes |
Yes |
Yes |
|
Diagnostics indication LED |
|||||
|
Yes |
Yes |
Yes |
Yes |
|
Parameter |
|||||
Remark |
4 byte |
12 bytes, 4 bytes in compatibility mode |
4 byte |
||
Diagnostics wire break |
Disable / enable (only in measuring range 1 to 5 V) |
At 4 to 20 mA |
|||
Measurement type/range |
deactivated / +/-5 V / 1 to 5 V / +/-10 V |
deactivated / +/-5 V / 1 to 5 V / +/-10 V |
deactivated / 4 to 20 mA |
4 to 20 mA, 0 to 20 mA |
|
Group diagnostics |
Disable / enable |
Disable / enable |
Disable / enable |
1 |
|
Overflow/underflow |
Disable / enable |
Disable / enable |
Disable / enable |
1 |
|
Potential separation |
|||||
Potential separation analog inputs |
|||||
|
No |
No; however, increased permissible potential difference between the inputs. |
No |
No |
|
|
Yes |
Yes |
Yes |
Yes |
|
|
Yes |
Yes |
No |
Yes |
|
Permissible potential difference |
|||||
between the inputs (UCM) |
140 V DC/100 V AC |
||||
Between the inputs and MANA (UCM) |
2 V AC PP |
||||
between MANA and M internally (UISO) |
75 V DC/60 V AC |
75 V DC/60 V AC |
|||
Isolation |
|||||
Isolation tested with |
500 V DC |
500 V DC |
500 V DC |
||
Dimensions |
|||||
Width |
15 mm |
15 mm |
15 mm |
15 mm |
|
Height |
81 mm |
81 mm |
81 mm |
81 mm |
|
Depth |
52 mm |
52 mm |
52 mm |
52 mm |
|
Weights |
|||||
Weight, approx. |
40 g |
45 g |
40 g |