西门子PLC
西门子PLC可编程控制器ET200S数字量模块
点击次数:38  发布时间:2018-03-19

西门子PLC可编程控制器ET200S数字量模块


西门子PLC可编程控制器ET200S数字量模块概述:

  • 用于 ET 200S 的 2、4 和 8 通道输入和输出

  • 采用自动编码,可插入到 TM-E 端子模板

  • 高性能型,用于增强设备可用性、附加功能和丰富的诊断功能

  • 可以进行模板的热交换

西门子PLC可编程控制器ET200S数字量模块技术规范:

Article number

6ES7131-4BB01-0AA0

6ES7131-4BB01-0AB0

6ES7131-4BD01-0AA0

6ES7131-4BD01-0AB0

6ES7131-4BD51-0AA0

6ES7131-4BF00-0AA0

 

ET200S, EL-MOD., 2DI ST, DC 24V, 5PCS.

ET200S, EL-MOD., 2DI HF, DC 24V, 5PCS.

ET200S, EL-MOD., 4DI ST., DC 24V, 5PCS.

ET200S, EL-MOD., 4DI HF, DC 24V, 5PC.

ET200S, EL-MOD., 4DI HF, DC 24V, 5PCS.

ET200S, ELEKTRONIKMODULE, 8DI DC 24V

Supply voltage

           

Rated value (DC)

           
  • ● 24 V DC

Yes; From power module

Yes; From power module

Yes; From power module

Yes; From power module

Yes; From power module

Yes

permissible range, lower limit (DC)

20.4 V

20.4 V

20.4 V

20.4 V

20.4 V

20.4 V

permissible range, upper limit (DC)

28.8 V

28.8 V

28.8 V

28.8 V

28.8 V

28.8 V

Reverse polarity protection

Yes

Yes

Yes

Yes

Yes

Yes

Input current

           

from supply voltage L+, max.

Dependent on encoder

Dependent on encoder

Dependent on encoder

Dependent on encoder

Dependent on encoder

Dependent on encoder

from backplane bus 3.3 V DC, max.

10 mA

10 mA

10 mA

10 mA

 

10 mA

Encoder supply

           

Number of outputs

         

0; no encoder supply

Type of output voltage

min. L+ (-0.5 V), under load

min. L+ (-0.5 V), under load

min. L+ (-0.5 V), under load

min. L+ (-0.5 V), under load

max. M +0.5 V, under load

 

Short-circuit protection

 

Yes; Electronic

 

Yes; Electronic

   

Output current

           
  • ● Rated value

500 mA

500 mA

500 mA

500 mA

500 mA

 
  • ● permissible range, lower limit

0 mA

0 mA

0 mA

0 mA

0 mA

 
  • ● permissible range, upper limit

500 mA

500 mA

500 mA

500 mA

500 mA

 

Power loss

           

Power loss, typ.

0.4 W

0.4 W

0.7 W

0.7 W

0.7 W

1.2 W

Address space per module

           
  • ● with packing

2 bit

2 bit

4 bit

4 bit

4 bit

 
  • ● without packing

1 byte

1 byte

1 byte

1 byte

1 byte

1 byte

Digital inputs

           

Number of digital inputs

2

2

4

4

4

8

Input characteristic curve in accordance with IEC 61131, type 1

Yes

Yes

Yes

Yes

Yes

Yes; 2-wire sensors connectable

Number of simultaneously controllable inputs

           
  • ● Number of simultaneously controllable inputs

         

8

Input voltage

           
  • ● Type of input voltage

DC

DC

DC

DC

DC

DC

  • ● Rated value (DC)

24 V

24 V

24 V

24 V

24 V

24 V

  • ● for signal "0"

-30 to +5V

-30 to +5V

-30 to +5V

-30 to +5V

-5 to +30V

-30 to +5V

  • ● for signal "1"

+15 to +30V

+11 to +30V

+15 to +30V

+11 to +30V

-15 to -30 V

+15 to +30V

Input current

           
  • ● for signal "1", typ.

7 mA; at 24 V

8 mA

7 mA; at 24 V

8 mA

7 mA; at 24 V

5 mA

Input delay (for rated value of input voltage)

           

for standard inputs

           
  • — parameterizable

No

Yes; 0.1 / 0.5 / 3 / 15 ms

No

Yes; 0.1 / 0.5 / 3 / 15 ms

No

No

  • — at "0" to "1", min.

2 ms; typically 3 ms

0.05 / 0.4 / 2.7 / 14.85

2 ms; typically 3 ms

0.05 / 0.4 / 2.7 / 14.85

2 ms; typically 3 ms

2 ms

  • — at "0" to "1", max.

4.5 ms

0,15 / 0,6 / 3,3 / 15,15

4.5 ms

0,15 / 0,6 / 3,3 / 15,15

4.5 ms

4.5 ms

  • — at "1" to "0", min.

2 ms; typically 3 ms

0.05 / 0.4 / 2.7 / 14.85

2 ms; typically 3 ms

0.05 / 0.4 / 2.7 / 14.85

2 ms; typically 3 ms

2 ms

  • — at "1" to "0", max.

4.5 ms

0,15 / 0,6 / 3,3 / 15,15

4.5 ms

0,15 / 0,6 / 3,3 / 15,15

4.5 ms

4.5 ms

Cable length

           
  • ● shielded, max.

1 000 m

1 000 m

1 000 m

1 000 m

1 000 m

1 000 m

  • ● unshielded, max.

600 m

600 m

600 m

600 m

600 m

600 m

Encoder

           

Connectable encoders

           
  • ● 2-wire sensor

Yes

Yes

Yes

Yes

Yes

Yes

  • — permissible quiescent current (2-wire sensor), max.

1.5 mA

1.5 mA

1.5 mA

1.5 mA

1.5 mA

1.5 mA

Isochronous mode

           

Isochronous operation (application synchronized up to terminal)

         

Yes; TWE = 3000 us

Interrupts/diagnostics/status information

           

Diagnostic functions

No

Yes

No

Yes

No

No

Alarms

           
  • ● Hardware interrupt

 

Yes; Parameterizable

       

Diagnostic messages

           
  • ● Short-circuit

 

Yes; Short-circuit of outputs to ground; module by module

 

Yes; Short-circuit of outputs to ground; module by module

   

Diagnostics indication LED

           
  • ● Group error SF (red)

No

Yes

No

Yes

No

 
  • ● Status indicator digital input (green)

Yes; per channel

Yes; per channel

Yes; per channel

Yes; per channel

Yes; per channel

Yes

Parameter

           

Remark

1 byte

3 byte

1 byte

3 byte

1 byte

3-byte parameter (not accessible for the user)

Diagnostics short-circuit

 

Disable / enable

 

Disable / enable

   

Potential separation

           

Potential separation digital inputs

           
  • ● between the channels

No

No

No

No

No

No

  • ● between the channels and backplane bus

Yes

Yes

Yes

Yes

Yes

Yes

Permissible potential difference

           

between different circuits

75 V DC/60 V AC

75 V DC/60 V AC

75 V DC/60 V AC

75 V DC/60 V AC

75 V DC/60 V AC

75 V DC/60 V AC

Isolation

           

Isolation tested with

500 V DC

500 V DC

500 V DC

500 V DC

500 V DC

500 V DC

Dimensions

           

Width

15 mm

15 mm

15 mm

15 mm

15 mm

15 mm

Height

81 mm

81 mm

81 mm

81 mm

81 mm

81 mm

Depth

52 mm

52 mm

52 mm

52 mm

52 mm

52 mm

Weights

           

Weight, approx.

35 g

35 g

35 g

35 g

35 g

35 g

 

Article number

6ES7131-4CD02-0AB0

6ES7131-4EB00-0AB0

6ES7131-4FB00-0AB0

6ES7131-4RD02-0AB0

6ES7131-4BF50-0AA0

 

ET200S, EL-MOD., 4DI, UC 24-48V, 5 PCS

ET200S, EL-MOD., 2DI, AC 120V, 5PCS.

ET200S, EL-MOD., 2DI, AC 230V, 5PCS.

ET200S, EL-MOD., 4DI DC 24V NAMUR

ET 200S, 8 DI Source Input DC24V

Supply voltage

         

Rated value (DC)

         
  • ● 24 V DC

Yes; From power module

   

Yes

Yes; From power module

permissible range, lower limit (DC)

24 V

   

20.4 V

20.4 V

permissible range, upper limit (DC)

48 V

   

28.8 V

28.8 V

Rated value (AC)

         
  • ● 24 V AC

Yes

       
  • ● 120 V AC

 

Yes; From power module

     
  • ● 230 V AC

   

Yes

   

permissible range, lower limit (AC)

24 V

102 V

192 V

   

permissible range, upper limit (AC)

48 V

144 V

264 V

   

Reverse polarity protection

Yes; AC or DC automatic

     

Yes

Input current

         

from supply voltage L+, max.

Dependent on encoder

     

Dependent on encoder

from supply voltage L1, max.

 

Dependent on encoder

Dependent on encoder

   

from backplane bus 3.3 V DC, max.

10 mA

6 mA

6 mA

   

Encoder supply

         

Number of outputs

     

1

 

Type of output voltage

min. L+ (-0.5 V), under load

   

min. 8.2 V, loaded

 

Short-circuit protection

Yes; per module

   

Yes; Electronic

 

Output current

         
  • ● Rated value

500 mA

   

45 mA

 
  • ● permissible range, lower limit

0 mA

       
  • ● permissible range, upper limit

500 mA

       

Power loss

         

Power loss, typ.

0.7 W

0.5 W

0.7 W

1.6 W

1.2 W

Address space per module

         
  • ● with packing

4 bit

2 bit

2 bit

4 bit

 
  • ● without packing

1 byte

1 byte

1 byte

1 byte

 

Digital inputs

         

Number of digital inputs

4

2

2

4

8

Number of NAMUR inputs

     

4

 

Parallel switching of inputs

     

No

 

Input characteristic curve in accordance with IEC 61131, type 1

Yes

Yes

Yes

 

Yes

Number of simultaneously controllable inputs

         
  • ● Number of simultaneously controllable inputs

     

4

 

Input voltage

         
  • ● Type of input voltage

AC/DC

AC

AC

DC

DC

  • ● Rated value (DC)

       

24 V

  • ● Rated value (AC)

 

120 V; 47 ... 63 Hz

230 V; 47 ... 63 Hz

   
  • ● Rated value (UC)

24 V

       
  • ● for signal "0"

-6 to +6 V DC/ 0 to 5 V AC

0V AC to 20V AC

0V AC to 40V AC

 

-5 to +30V

  • ● for signal "1"

-15 V DC to -57.6 V DC; 15 V DC to 57.6 V DC; 15 V AC to 48 V AC

79 to 132 V AC

164V AC to 264V AC

 

-15 to -30 V

Input current

         
  • ● for signal "1", typ.

10 mA; 4 to 10 mA

3 mA; 3 to 9 mA

5 mA; 5 to 15mA

 

6 mA; at 24 V

for 10 k switched contact

         
  • — for signal "0"

     

0.35 to 1.2 mA

 
  • — for signal "1"

     

2.1 to 7 mA

 

for unswitched contact

         
  • — for signal "0", max. (permissible quiescent current)

     

0.5 mA

 
  • — for signal "1"

     

typ. 8 mA

 

for NAMUR encoders

         
  • — for signal "0"

     

0.35 to 1.2 mA

 
  • — for signal "1"

     

2.1 to 7 mA

 

Input delay (for rated value of input voltage)

         

for standard inputs

         
  • — parameterizable

       

No

  • — at "0" to "1", min.

 

15 ms

15 ms

 

2 ms

  • — at "0" to "1", max.

15 ms

   

4.6 µs

4.5 ms

  • — at "1" to "0", min.

 

25 ms

45 ms

 

2 ms

  • — at "1" to "0", max.

15 ms

   

4.6 µs

4.5 ms

Encoder connection

         
  • ● Fixed current limitation for wire-break monitoring, min.

18 kΩ; Rated voltage 24 V (15 V to 35 V); rated voltage 48 V (30 V to 60 V): 39 kohms

       

Cable length

         
  • ● shielded, max.

1 000 m

1 000 m

1 000 m

200 m

1 000 m

  • ● unshielded, max.

600 m

600 m

600 m

 

600 m

Encoder

         

Connectable encoders

         
  • ● 2-wire sensor

Yes

No

No

 

Yes

  • — permissible quiescent current (2-wire sensor), max.

2 mA; (0.5 to 2 mA), a minimum load current is necessary for wire break diagnostics.

1 mA

2 mA

 

1.5 mA

Isochronous mode

         

Isochronous operation (application synchronized up to terminal)

Yes

No

No

 

Yes

Interrupts/diagnostics/status information

         

Diagnostic functions

Yes; Parameterizable

No

No

Yes; Diagnostic alarm

No

Alarms

         
  • ● Diagnostic alarm

     

Yes; can be set

 
  • ● Hardware interrupt

     

No

 

Diagnostic messages

         
  • ● Diagnostic information readable

     

Yes

 
  • ● Wire-break

Yes

   

Yes

 
  • ● Short-circuit

 

No

No

   

Diagnostics indication LED

         
  • ● Group error SF (red)

Yes

   

Yes

No

  • ● Status indicator digital input (green)

Yes; per channel

Yes; per channel

Yes; per channel

Yes; per channel

Yes; per channel

Parameter

         

Remark

 

3 byte

3 byte

12 byte

3 byte

Potential separation

         

Potential separation digital inputs

         
  • ● between the channels

No

No

No

No

No

  • ● between the channels and backplane bus

Yes

Yes

Yes

Yes

Yes

  • ● Between the channels and load voltage L+

     

Yes

 

Permissible potential difference

         

between different circuits

75 V DC/60 V AC

   

75 V DC/60 V AC

75 V DC/60 V AC

between M internally and the inputs

 

1500 V AC

1500 V AC

   

Isolation

         

Isolation tested with

2500 V DC

2500 V DC

4 000 V DC

500 V DC

500 V DC

Dimensions

         

Width

15 mm

15 mm

15 mm

15 mm

15 mm

Height

81 mm

81 mm

81 mm

81 mm

81 mm

Depth

52 mm

52 mm

52 mm

52 mm

52 mm

Weights

         

Weight, approx.

35 g

31 g

31 g

35 g

35 g


相关产品:西门子PLC 

  • QQ咨询

  • 在线咨询
  • 点击这里给我发消息
友情链接: 工控文章